Lucene search

K
RockwellautomationFactorytalk Linx*

6 matches found

CVE
CVE
added 2020/11/26 2:15 a.m.74 views

CVE-2020-27251

A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution.

9.8CVSS9.7AI score0.16799EPSS
CVE
CVE
added 2020/11/26 2:15 a.m.70 views

CVE-2020-27253

A flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to specifically craft a malicious packet resulting in a denial-of-service condition on the device.

7.8CVSS7.4AI score0.00033EPSS
CVE
CVE
added 2020/11/26 2:15 a.m.66 views

CVE-2020-27255

A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious set attribute requests, which could result in the leaking of sensitive information. This information disclosure could lead to the ...

7.5CVSS7.4AI score0.01516EPSS
CVE
CVE
added 2020/12/29 4:15 p.m.57 views

CVE-2020-5802

An attacker-controlled memory allocation size can be passed to the C++ new operator in RnaDaSvr.dll by sending a specially crafted ConfigureItems message to TCP port 4241. This will cause an unhandled exception, resulting in termination of RSLinxNG.exe. Observed in FactoryTalk 6.11. All versions of...

7.5CVSS7.4AI score0.00168EPSS
CVE
CVE
added 2020/12/29 4:15 p.m.53 views

CVE-2020-5801

An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected...

7.5CVSS7.4AI score0.00221EPSS
CVE
CVE
added 2020/12/29 4:15 p.m.38 views

CVE-2020-5806

An attacker-controlled memory allocation size can be passed to the C++ new operator in the CServerManager::HandleBrowseLoadIconStreamRequest in messaging.dll. This can be done by sending a specially crafted message to 127.0.0.1:7153. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Li...

5.5CVSS5.4AI score0.00005EPSS